Accessory

ECB/ECBA


Feature

  • Control panel for water supply from reservoir to elevated water tank, for Individual operation and Alternate operation.
  • A variety of indicate lamps and voltage free terminals are equipped for operation signal, as well as alarm signal of reservoir empty and full, elevated water tank low and full, and so on.
  • Alternate operation type has automatic faulty pump skip function just in case for pump failure during operation.
  • In Alternate operation type, for submersible pump type is available as well as for ground pump. A variety of custom models are prepared in addition to standard model.

Standard spec

Operation method
Alternate
Control method
ON-OFF according to water level of reservoir and elevated water tank
Rated capacity
1.5 to 3.7kW
Frequency
50Hz, 60Hz
Ambient temperature
-5 to 40°C
Percentage of humidity
45 to 85%RH
Protective devise
3E relay
Installation location
Indoor
Material of box (thickness)
Box: SPC (1.6t)
Door: SPC (1.6t)
Inner plate: SPC (2.3t)
Paint color (Munsell No.)
Beige (5Y7/1)
Indication lamp
Power (white), Run (red),: Individual indication with No.1 & No.2 lamp in alternate operation model, Trouble (orange), Reservoir (orange): individual indication of full&empty,Elevated water tank (orange): individual indication of full&low: (White)
External signal (no voltage)
Run/ Trouble/ Reservoir full/ Reservoir empty/ Elevated tank full/ Elevated tank low
Float less switch
Level relay
Start-up method
Direct start

Optional Accessories

Level relay
Electrode
Electrode holder (use without resistor type.)